Part Number Hot Search : 
R5D10 B4226 R1EX240 ST485EC EP9154 HCF4032 025001 TMG16D60
Product Description
Full Text Search
 

To Download WFD30-2E Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 WFDE Series Waterflow Detector
System Sensor's WFDE series is compatible with pipe diameters ranging from 50mm through 200mm and can be mounted in a vertical or horizontal position.
Features
* Compliant with Construction Products Directive * EC Certificate Number 0786-CPD-40151 * WFD30-2E models install in 50.8mm (2") hole sizes * IP54 rated enclosure * Sealed retard mechanism assures that the retard is not contaminated by dust and dirt when the cover is removed * Visual switch activation permits installer to accurately set the retard even under extremely noisy conditions * Rugged, dual SPDT switches are enclosed in a durable terminal block for added strength * 100% synchronization activates both alarm panel and local bell simultaneously
Robust Construction. The WFDE series consists of a rugged, IP54 rated enclosure. Designed for both indoor and outdoor use, the WFDE series operates across a wide temperature range, from 0C to 68C (32F to 155F). Reliable Performance. WFDE models are equipped with tamperresistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block to ensure reliable performance. False Alarm Immunity. The WFDE series incorporates a mechanical retard feature, which minimizes the risk of false alarm due to pressure surges or air trapped in the sprinkler system. In addition, the mechanical retard's unique sealed design is immune to dust and other contaminants. Simplified Operation. The WFDE series is designed to simplify installation. Two conduit openings permit easy attachment to the local alarm system. The retard mechanism and dual SPDT switches are field-replaceable.
Agency Listings
VdS
TE83724 G4940006 1Z0A7.AH
Scientific Services Laboratory
afp-836
0786
Waterflow Detector Specifications
Engineering Specifications Vane-type System Sensor WFDE series waterflow detectors shall be installed on system piping as designated on the drawings and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 15 cm (6 in.) from any fittings, which may change water direction, flow rate or pipe diameter, or no closer than 61 cm (24 in.) from a valve or drain. The detector shall respond to waterflow in the specified direction after a preset time delay, which is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances (one of which is a knockout type) for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. WFDE waterflow detectors shall be approved by Factory Mutual, LPC, VdS and SSL. Standard Specifications Static Pressure Rating Triggering Threshold Bandwidth (Flow Rate) Contact Ratings; Two sets of SPDT (Form C) Conduit Entrances Operating Temperature Range Enclosure Rating Shipping Weight U.S. Patent Numbers Warranty Compatible Pipe Model Ref. Pipe Size mm (in.) Nominal Pipe O.D. (mm) LPC VdS 60.3 60.3 76.0 76.1 88.8 88.9 114.1 114.3 165.1 168.3 219.1 219.1 WFD30-2E WFD40E 2.05 kg (4.53 lbs.) 2.36 kg (5.20 lbs.) Wall Thickness (mm) LPC VdS 3.6 2.3/2.9 3.6 2.6/2.9 4.0 2.9/3.2 4.5 3.2/3.6 5.0 4.0/4.5 6.3 4.5/5.9 WFD60E 3.03 kg (6.68 lbs.) WFD80E 3.45 kg (7.70 lbs.)
To power source compatible with bell
B
LPC: 17.25 BAR (250 PSI) VdS: PN16 (16 BAR, 232 PSI) 30-57 liters/minute 10.0 A @ 125/250 VAC 2.5 A @ 24 VDC Two openings 22.2mm (.875 in.) diameter. One open, one knock-out type 0C to 68C (32F to 155F) IP54 WFD20E: 1.85 kg (4.08 lb.); WFD25E: 1.85 kg (4.08 lb.); WFD30-2E: 2.05 kg (4.53 lb.); WFD40E: 2.36 kg (5.20 lb.); WFD60E: 3.03 kg (6.68 lb.); WFD80E: 3.45 kg (7.70 lb.) 5,213,205; 4,782,333; 3,845,259 3 Years
WFDE Field Wiring Diagram
A B B A
WFD20E 50 (2) WFD25E 65 (21/2) WFD30-2E 80 (3) WFD40E 100 (4) WFD60E 150 (6) WFD80E 200 (8) Shipping Weight WFD20E Model WFD25E 1.85 kg (4.08 lbs.)
SWITCH 1
M CO -CAUTION-
ROUTE WIRING AWAY FROM SHARP EDGES & COMPONENTS
SWITCH 2 SWITCH SCHEMATIC CO "READY" STATE M
A COM B T16-0010-XXX
NOTE: Common and B connections will close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector.
CONTACT RATINGS 125/250 VAC 10 AMPS 24 VDC 2.5 AMPS WFDE
B B
WFDE
B B
To nonsilenceable initiating zone of listed FACP
end-of-line resistor
COM COM COM COM
Typical FACP Connection
local bell
COM
Delay Adjustment Dial
Delay adjustment dial
WFDE switch assembly Typical Local Bell Connection
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
0
Dial setting
0
5
10
15
20
25
Ordering Information Model Pipe Size WFD20E 50mm (2") WFD25E 65mm (21/2") WFD30-2E 80mm (3") WFD40E 100mm (4") WFD60E 150mm (6") WFD80E 200mm (8")
5
25
Hole Size 31.8mm (11/4") 31.8mm (11/4") 50.8mm (2") 50.8mm (2") 50.8mm (2") 50.8mm (2")
10
20
Dial setting equals delay in seconds. Reference only.
15
3825 Ohio Avenue * St. Charles, IL 60174 Phone: 800-SENSOR2 * Fax: 630-377-6495
(c)2006 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0243-007 * 7/06 * #1679


▲Up To Search▲   

 
Price & Availability of WFD30-2E

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X